Specifications
Gas Detected | Ozone | ||
Sensing Element | Electrochemical gas sensor | ||
Sensor lifetime | >2 years, removable | ||
Temperature Sensor | NTC | ||
Humidity Sensor | HS series capacitive sensor | ||
Power Supply | 24VAC/VDC (power adaptor selectable) | ||
Power Consumption | 2.8W | ||
Response Time | <50s @T90 | ||
Signal Update | 1s | ||
Warm up Time | <60 seconds | ||
Ozone Measuring Range | 0~5000ppb (0-5ppm)( 0~9.81mg/m3) | ||
Display Resolution | 1ppb (0.001ppm) (0.01mg/ m3) | ||
Accuracy | ±0.01ppm + 10% reading | ||
Nonlinear | <1%FS | ||
Repeatability | <0.5% | ||
Zero Drift | <1% | ||
Alarm | Buzzer and Yellow or Red backlight switch | ||
Display | Green-normally, Orange – first stage alarm, Red- second stage alarm. | ||
Temperature/humidity Measuring Range | 5~60 (41~140)/0~80%RH | ||
Analog Output | 010VDC(default) or 4~20mA linear output selectable | ||
Analog Output Resolution | 16Bit | ||
Relay dry contact Output | Two dry-contact outputs | ||
Modbus Communication Interface | Modbus RTU protocol with 19200bps(default) | ||
Working Condition/Storage Conditions | 5~60 (41~140)/ 0~ 80% RH | ||
Net Weight | 190g | ||
Dimensions | 130mm(H)×85mm(W)×36.5mm(D) | ||
Installation Standard | 65mm×65mm or 85mmx85mm or 2”×4” wire box | ||
Interface Connection (Max) | 9 terminals | ||
Wiring Standard | Wire section area<1.5mm2 | ||
Manufacturing Process | ISO 9001 Certified | ||
Housing and IP class |
Company QR code Anytime Anywhere Mobile |